Main Features
- Compact Design
- Multiple Protection Functions
- Wide Current Adjustment Range(10:1)
- Ammeter Function
- Trip Indication LED
- High Accuracy
- Manual Instantaneous Reset
- Electrical Remote Reset
- Test Function
- Ambient Insensitive
- Low Energy Consumption
- Fail-safe Operation(No Volt Release)
- 2 Integral CTs
- Fit Directly info IEC or NEMA Contactor
Protection
Protective Item |
Operating(Trip) Time |
Over-current |
O-TIME |
Phase Loss |
O-TIME |
Locked Rotor |
O-TIME |
Specficication
Current Setting |
Type |
Range |
01 |
0.3 ~ 1.2A |
|
10 |
1 ~ 12A |
|
20 |
5 ~ 25A |
|
Time Setting |
O-TIME |
0.5 ~ 15sec |
Control Voltage |
220 |
90 ~260VAC |
440 |
320 ~ 480VAC |
|
Output Relay |
Mode |
1-SPDT(1C) |
Rating |
3A / 250VAC Resistive |
|
Status |
Normally Energized With Power |
|
Time-Current Characteristic |
Definite |
|
Operating(Trip) Indication |
2-LED |
|
Mounting |
Contactor Mounted |
Curve : please contact
Diagram : please contact